Power Substation Type Polymer Lightning Arrester

(0 reviews)

Sold by:
Inhouse product

Price:
ASK Price /pcs

Quantity:
(120 available)

Total Price:
ASK Price
Share:

Product Details:

Power Substation Type Polymer Lightning Arrester

 

General Introduction

Wolun Polymer Lightning Arresters are manufactured to offer optimum protection to distribution equipment such as transformers and similar assets against the damaging lightning effects and similar operational conditions. These arresters perform their task with high-end improvement and fidelity towards surge switching and medium voltage networks. Maintenance of service safety for both underground and overheard setups is offered without any trouble on exposure in the outdoors for long durations. Going through precision tests have made Wolun arresters more durable & reliable.

 

Working Conditons

1. The ambient air temperature is no higher than +40°C, no lower than -40 °C .

2. The altitude above sea level does not exceed 1000m. ( the plateau area should be indicated when order.)

3. AC system frequency is 50Hz or 60Hz.

4. Power frequency voltage brought to bear on arrester for a long time does not exceed the continuous operation voltage of the arrester.

5. Maximum wind speed does not exceed 35m/s.

6. Te earthquake intensity does not exceed 7 degrees.

7. The pollution area should be indicated.

 

Features

  • It adopts double sealing structure, the core encapsulates by molded silicone rubber which completely solves the sealing problem of porcelain housed products.
  • It has a two-way pressure release structure.
  • Its core component ZnO varistor has good pressure ratio, consistency, large flow capacity and high reliability.
  • E creepage distance of porcelain housed products is wide which is suitable for IV level heavy pollution areas.

 

Technical Specification

 

TypeNominal System VoltageRated VoltageContinuous Operating VoltageMRV under 1/5 μ s Steeo Discharge CurrentMRV under 8/20 μ s Lightning Discharge CurrentMRV under 30/60 μ s Operating Discharge CurrentMinmum Reference Voltage under 1 mA DC4/10 μ s High Current Impulse Twice (KA)2mS

SW through-flow capacity A/18

Line Discharge Class
10KA20KA5KA10KA0.5KA1KA
Y10W5-102/266123102812772352582032101481008503
Y10W5-108/281145108862952492742152221571008503
Y10W5-111/290145111883032572822222291611008503
Y10W5-120/313145120983272773042392471741008503
Y10W5-126/3291451261003442913202512591831008503
Y10W5-132/3441451321063593053342632721921008503
TypeNominal System VoltageRated VoltageContinuous Operating VoltageMRV under 1/5 μ s Steeo Discharge CurrentMRV under 8/20 μ s Lightning Discharge CurrentMRV under 30/60 μ s Operating Discharge CurrentMinmum Reference Voltage under 1 mA DC4/10 μ s High Current Impulse Twice (KA)2mS SW through-flow capacity A/18Line Discharge Class
5KA10KA5KA10KA0.25KA0.5KA
Y10W5-192/5002201921505605004262801008003
Y10W5-200/5202202001565825204422901008003
Y10W5-204/5322202041595945324522961008003
Y10W5-216/562220216168.56305624783141008003

 

TypeNominal System VoltageRated VoltageContinuous Operating VoltageMRV under 1/5 μ s Steeo Discharge CurrentMRV under 8/20 μ s Lightning Discharge CurrentMRV under 30/60 μ s Operating Discharge CurrentMinmum Reference Voltage under 1 mA DC4/10 μ s High Current Impulse Twice (KA)2mS SW through-flow capacity A/18Line Discharge Class
10KA20KA10KA20KA0.5KA2KA
Y10W5-420/960500420318107596085256510015004
Y20W5-420/10465004203181070104685856510020005
Y10W5-444/10155004443241137101590059710015004
Y20W5-444/11065004443241238110690759710020005
Y10W5-468/10705004683301198107095063010015004
Y20W5-468/11665004683301306116695663010020005

 

 